The size carries over from the Size the system tab. Prices are for a central AC, unit plus installation, before any duct or electrical work.
See full breakdown
One ton of cooling equals 12,000 BTU per hour. Most homes land between 1.5 tons for 600 to 1,100 sq ft and 5 tons for 2,401 to 3,300 sq ft, and a hot climate needs the bigger size for the same floor area. Heating runs about 30 to 35 BTU per sq ft in mild zones and up to 50 to 60 in very cold ones. Do not round up for safety: an oversized unit short cycles, wastes energy and leaves the house humid. A Manual J load calculation confirms the final size.
How to calculate HVAC size
Sizing starts from floor area and climate, then adjusts for the house itself. This AC size calculator runs the cooling side and the heating side together, so the AC and the furnace come out matched to the same home.
| Cooling AC or heat pump, in tons | Heating furnace, in BTU per hour | |
|---|---|---|
| Starting point | Tons from the size chart for your floor area and zone, × 12,000 BTU/h per ton | Floor area × BTU per sq ft for your zone, from 30 in Zone 1 up to 60 in Zone 5 |
| Ceiling height | × ceiling height ÷ 8 ft | × ceiling height ÷ 8 ft |
| Sun and windows | × 0.9 if heavily shaded, × 1.1 if very sunny | Not counted |
| People and kitchen | + 600 BTU/h for each person beyond two, + 4,000 for an open kitchen | Not added |
| Insulation | Decides which size inside the fitting range you take | Low end of the zone range if well insulated, high end if poor, middle if average |
| Final size | Standard size between 95% and 115% of the load (heat pumps up to 125%) | Furnace output between 100% and 140% of the load; input rating = output ÷ AFUE |
Worked example: 1,800 sq ft in Zone 3, 8 ft ceilings, average sun and insulation, four people
The heating side for the same house: 1,800 sq ft × 42.5 BTU per sq ft = 76,500 BTU/h of output, which a 95% AFUE furnace delivers from about 80,500 BTU/h of input.
When to use this HVAC sizing calculator
Use it before money changes hands on a new system, or any time a size on paper needs a second look.
- Choosing a new unit: shopping for an AC, heat pump or furnace starts with the size, and the size decides which models are even on the table. Run your house here first so the brochures and quotes you collect all point at the same tonnage.
- Checking a contractor's recommendation: pick the size from the quote in the last field and the calculator tells you whether it sits inside the range for your home. A unit well above the range is the classic oversizing mistake, and it is worth a question before you sign.
- Planning a renovation or addition: see whether the extra square footage pushes you into the next size.
- Quick numbers before quotes: walk into the first sales visit already knowing the ballpark.
- Comparing against benchmarks: line your result up with the zone size chart and the heating BTU per sq ft range below. If your home needs far more than the chart suggests, something like a leaky attic or a wall of west facing glass is usually behind it.
- Replacing an old system: read the tonnage off your outdoor unit's model number and compare it with the size this AC size calculator suggests.
- Mobile and manufactured homes: switch the home type and the size moves up to match how these homes are usually fitted.
- Pre bid estimates for HVAC contractors: size a replacement from the driveway before the full load calculation, then flip to Price the new AC to see where a proposal sits against typical installed prices for that tonnage. It keeps the first conversation with the homeowner grounded in numbers they can check.
What size AC do I need for my square footage?
Find your floor area in your climate zone column and read the size on the left. The same 3 tons covers up to 1,800 sq ft in the hottest zone and up to 2,100 sq ft in the coldest.
| AC size | Zone 1 | Zone 2 | Zone 3 | Zone 4 | Zone 5 |
|---|---|---|---|---|---|
| 1.5 tons | 600 to 900 | 600 to 950 | 600 to 1,000 | 700 to 1,050 | 700 to 1,100 |
| 2 tons | 901 to 1,200 | 951 to 1,250 | 1,001 to 1,300 | 1,051 to 1,350 | 1,101 to 1,400 |
| 2.5 tons | 1,201 to 1,500 | 1,251 to 1,550 | 1,301 to 1,600 | 1,351 to 1,600 | 1,401 to 1,650 |
| 3 tons | 1,501 to 1,800 | 1,501 to 1,850 | 1,601 to 1,900 | 1,601 to 2,000 | 1,651 to 2,100 |
| 3.5 tons | 1,801 to 2,100 | 1,851 to 2,150 | 1,901 to 2,200 | 2,001 to 2,250 | 2,101 to 2,300 |
| 4 tons | 2,101 to 2,400 | 2,151 to 2,500 | 2,201 to 2,600 | 2,251 to 2,700 | 2,301 to 2,700 |
| 5 tons | 2,401 to 3,000 | 2,501 to 3,100 | 2,601 to 3,200 | 2,751 to 3,300 | 2,701 to 3,300 |
Square feet of living space, standard 8 ft ceilings. Zone 1 takes in Florida, Louisiana and most of Texas; Zone 2 most of California; Zone 3 Kansas, Kentucky and Virginia; Zone 4 Colorado, Ohio, Pennsylvania and New Jersey; Zone 5 Minnesota, Michigan, New York and the Pacific Northwest.
How many BTU do I need to heat my house?
Multiply your floor area by the BTU per sq ft for your zone. Take the low number for a well insulated home with modern windows and the high number for an older home with single pane glass.
| Zone | BTU per sq ft | 1,500 sq ft home | 2,000 sq ft home |
|---|---|---|---|
| Zone 1, hottest | 30 to 35 | 45,000 to 52,500 | 60,000 to 70,000 |
| Zone 2, hot | 35 to 40 | 52,500 to 60,000 | 70,000 to 80,000 |
| Zone 3, warm | 40 to 45 | 60,000 to 67,500 | 80,000 to 90,000 |
| Zone 4, cool | 45 to 50 | 67,500 to 75,000 | 90,000 to 100,000 |
| Zone 5, coldest | 50 to 60 | 75,000 to 90,000 | 100,000 to 120,000 |
Figures are heat output in BTU per hour at 8 ft ceilings. Taller ceilings mean more air to heat, so scale up by your ceiling height ÷ 8.
What sizes do central AC units come in?
Home systems step up in half tons from 1.5 to 4, then jump to 5. You buy the standard size that fits your load, never the exact number.
| Size | Cooling capacity | Code in the model number | Floor area it covers, all zones |
|---|---|---|---|
| 1.5 tons | 18,000 BTU/h | 18 | 600 to 1,100 sq ft |
| 2 tons | 24,000 BTU/h | 24 | 901 to 1,400 sq ft |
| 2.5 tons | 30,000 BTU/h | 30 | 1,201 to 1,650 sq ft |
| 3 tons | 36,000 BTU/h | 36 | 1,501 to 2,100 sq ft |
| 3.5 tons | 42,000 BTU/h | 42 | 1,801 to 2,300 sq ft |
| 4 tons | 48,000 BTU/h | 48 | 2,101 to 2,700 sq ft |
| 5 tons | 60,000 BTU/h | 60 | 2,401 to 3,300 sq ft |
What happens if your AC or furnace is the wrong size?
Too big is the more common mistake, and it is not a safety margin. A unit that is too large cools the air fast, shuts off before it pulls out the moisture, and starts again a few minutes later.
| Too big | Too small | |
|---|---|---|
| How it runs | Short cycles: on and off again and again without a full run | Runs constantly and still misses the set temperature on the hottest or coldest days |
| How the house feels | Cold but clammy in summer, uneven rooms in winter | Cold spots and rooms that never catch up |
| What it costs you | Units oversized by 50% or more used about 9% more cooling electricity a year in one Florida study, and every extra start wears the compressor | Nonstop running adds strain that can shorten the system's life |
How much bigger than the load a unit can be
| Equipment | Capacity that fits the load |
|---|---|
| Central AC | 95% to 115% of the cooling load, or the next standard size up |
| Heat pump | Up to 125% of the cooling load, or the next standard size up |
| Furnace | 100% to 140% of the heating load |
What changes the HVAC size a house needs?
Floor area and climate set the starting size. Everything below nudges it up or down, and a few of these together can move a home a full size.
| Factor | What changes the size | Typical effect |
|---|---|---|
| Climate zone | Hot zones need more cooling for each square foot and cold zones need more heating. | 3 tons covers up to 1,800 sq ft in Zone 1 and 2,100 in Zone 5 |
| Floor area | Living space only. Leave out the garage and any unconditioned rooms. | 1.5 tons from 600 sq ft up to 5 tons at 3,300 |
| Ceiling height | Size charts assume 8 ft. A taller room holds more air, so both the AC and the furnace have more to condition. | Load × height ÷ 8: 10 ft ceilings add 25% |
| Insulation and windows | A tight, modern home sits at the low end of every range. Older homes with single pane windows or air leaks sit at the high end. | Heating in Zone 3: 40 BTU per sq ft well insulated, 45 poorly |
| Sun exposure | Heavy shade takes load off. A very sunny house with lots of glass adds it. | Cooling 10% lower or 10% higher |
| People | Every person gives off heat the AC has to remove. | +600 BTU/h for each person beyond two |
| Kitchen | Cooking heat in an open kitchen lands on the same system. | +4,000 BTU/h |
| Type of home | Mobile and manufactured homes are usually fitted bigger than site built houses of the same size. Never size one below the tonnage it has now. | ½ to 1 ton larger |
| Stories | The second floor acts as insulation for the first. | Downstairs equipment carries less load |
| Furnace efficiency | AFUE is the share of the fuel that ends up as heat in the house. | 80% AFUE: 100,000 BTU in, 80,000 out |
When do you need a Manual J load calculation?
A size chart is a fast first answer. A Manual J works out the real heat gain and heat loss from your walls, windows, insulation and local design temperatures, and a contractor who sizes by square footage alone, or swaps in whatever was there before, is skipping it.
- New constructionThere is no old unit to go by, so the load has to come from the plans.
- Additions and major renovationsNew floor area, a finished attic or a wall of new windows changes the load. Size from the house as it will be, not as it was when the old unit went in.
- A system that never kept upIf the old unit short cycled or never held temperature, copying its size repeats the problem.
- After insulation or window upgradesA tighter shell can need a smaller unit than the one it has now.
- Homes past the chartAbove 3,300 sq ft the size chart runs out, and a single home unit tops out at 5 tons. A house that size needs a proper design, not a chart lookup.
- Mobile and manufactured homesSquare foot charts do not fit them well.
Want the heat gain and heat loss numbers first? Run them in our HVAC load calculator, then come back here to turn the load into an equipment size.
How much does a new AC cost by size?
A new central AC runs about $2,000 to $5,000 installed at 1.5 tons and $4,000 to $8,000 at 5 tons. Each step up costs more, so an oversized unit costs you once at purchase and again on every bill.
| Size | Cooling capacity | Typical installed cost |
|---|---|---|
| 1.5 tons | 18,000 BTU/h | $2,000 to $5,000 |
| 2 tons | 24,000 BTU/h | $2,500 to $5,500 |
| 2.5 tons | 30,000 BTU/h | $2,700 to $6,000 |
| 3 tons | 36,000 BTU/h | $3,000 to $6,500 |
| 3.5 tons | 42,000 BTU/h | $3,100 to $7,000 |
| 4 tons | 48,000 BTU/h | $3,500 to $7,500 |
| 5 tons | 60,000 BTU/h | $4,000 to $8,000 |
Unit plus standard installation. Brand, efficiency, access and local labor rates move the price, and new duct work can add over $1,000 on its own.
HVAC owners: a replacement quote goes cold the day nobody calls back.
Homeowners pricing a new system often collect two or three bids, and a job worth thousands can slip away while your techs are busy on other calls. ServiceAgent answers the first call at any hour, books the in home sizing visit on your calendar, and keeps following up on every open replacement quote by phone and text until the customer gives you an answer.
Book a free demoFrequently asked questions
Plain answers on AC tonnage, furnace BTU and picking the right equipment size.
Book a free demoWhat is the formula for sizing an HVAC system?
Take the tons the size chart gives for your floor area and climate zone and multiply by 12,000 to get BTU per hour. Scale that by your ceiling height ÷ 8, take 10% off for heavy shade or add 10% for a very sunny house, then add 600 BTU/h for each person beyond two and 4,000 for an open kitchen. Pick the standard size between 95% and 115% of the result. For the furnace, multiply floor area by 30 to 60 BTU per sq ft depending on your zone. If your local code or an engineer gives you a different BTU per sq ft figure, that is the number to swap in.
What size AC does a 2,000 sq ft house need?
Usually 3 to 3.5 tons. In Zones 1, 2 and 3 a 2,000 sq ft home falls in the 3.5 ton row of the size chart, and in Zones 4 and 5 it falls in the 3 ton row. High ceilings, a sunny lot or a full house can push it up one size.
How many square feet will a 3.5 ton AC cool?
About 1,801 to 2,300 sq ft. In the hottest zone a 3.5 ton unit covers 1,801 to 2,100 sq ft, and in the coldest it stretches to 2,101 to 2,300 sq ft.
How accurate is this HVAC size calculator?
It gives a solid rule of thumb size, not a final design. It does not count duct losses, window by window heat gain or local design temperatures, so treat the result as the size to expect on a quote and let a Manual J load calculation confirm it before you buy.
Is a bigger AC better?
No. An oversized AC short cycles, shuts off before it removes the humidity and wears the compressor with extra starts. In one Florida study, units oversized by 50% or more used about 9% more cooling electricity a year. The right unit lands between 95% and 115% of the cooling load.
What is the $5,000 rule for HVAC?
Multiply the age of your system by the repair estimate. If the answer is over $5,000, replacing usually makes more sense; under $5,000, repair it. A 12 year old unit with a $500 repair scores 6,000, so it is time to price a new one, and this calculator tells you what size to price. It is a guideline, not a hard rule.
Can I use this AC size calculator for an apartment or a single room?
Yes. Enter the floor area and the number of people who live there. Below 600 sq ft the size chart for central systems runs out, so the space is sized like a room: 450 to 550 sq ft needs about 12,000 BTU/h, which suits a mini split or room unit.
Does it work for light commercial buildings?
For a small office or shop it gives a reasonable starting size. Larger commercial projects need a detailed engineering load calculation, because people, equipment and ventilation loads are very different from a home.
How do I find the size of my current AC?
Check the model number on the outdoor unit, not the serial number. Find the two digit code such as 18, 24, 30, 36, 42, 48 or 60 and divide it by 12: 36 means 36,000 BTU/h, a 3 ton unit.
Should I replace my AC with the same size?
Usually, yes. Keep the current tonnage unless you added square footage, had steady comfort problems, or made major insulation upgrades since the old unit went in. For a mobile or manufactured home, do not go below the tonnage it has now.
Leads growth and product marketing for ServiceAgent at SaaS Labs, where he has worked in product marketing since 2020. Writes ServiceAgent's coverage of AI call answering, CRM and home services operations.
NATE certified Master HVAC Technician with 14 years in residential and light commercial HVAC. Former Senior Service Tech at Trane Austin, now reviews HVAC content for ServiceAgent.
Published by ServiceAgent, the AI front office for home service teams. Sizes and prices are estimates for planning. The final equipment size should come from an ACCA Manual J load calculation and Manual S selection for the actual house, and the price you budget for should be the one on a contractor's written quote.